To adjust alarm settings:
By default, the alarm is ON.
Press and hold the Select button for two seconds. The screen will display one of two things:
AL0” – this indicates the alarm is OFF
AL1” – this indicates the alarm is ON
The screen will display the setting (either AL0 or AL1) briefly and then return to the previous
screen.
Note: The alarm setting will revert back to default (ON) when the Inverter button is turned OFF
then ON again.
To adjust the charging current:
By default, the charging current is as follows:
20A for the 12-110-1000-B2
40A for the 12-110-1800-B4, 12-110-1000-B4
1. Press and hold the Inverter button for five seconds. This brings the inverter into Charge
Current Setting Mode.
2. Press the Select button to switch between the different current ratings in [Amps].
2 – 5 – 10 – 20 for the 12-110-1000-B2
2 – 10 – 20 – 40 for the 12-110-1800-B4, 12-110-1000-B4
3. To choose a current setting, stop at the value displayed and wait five seconds to set it.
Once the current is set, the display will return to the previous screen.
Unit performance can be maximized using Table 3-1 below.